home *** CD-ROM | disk | FTP | other *** search
/ Internet Surfer 2.0 / Internet Surfer 2.0 (Wayzata Technology) (1996).iso / pc / text / mac / faqs.032 < prev    next >
Text File  |  1996-02-12  |  29KB  |  598 lines

  1. Frequently Asked Questions (FAQS);faqs.032
  2.  
  3.  
  4.  
  5.     The two pairs of connections on a GFCI outlet are not symmetric.
  6.     One is labeled LOAD; the other, LINE.  The incoming power feed
  7.     *must* be connected to the LINE side, or the outlet will not be
  8.     protected.  The LOAD side can be used to protect all devices
  9.     downstream from it.  Thus, a whole string of outlets can be
  10.     covered by a single GFCI outlet.
  11.  
  12. Subject: Where should GFCIs be used?
  13.  
  14.     The NEC mandates GFCIs for 110V, 15A or 20A single phase
  15.     outlets, in bathrooms, kitchens within 6' of the sink, garages,
  16.     unfinished basements or crawl spaces, outdoors, near a pool, or
  17.     just about anywhere else where you're likely to encounter water
  18.     or dampness.  There are exceptions for inaccessible outlets,
  19.     those dedicated to appliances ``occupying fixed space'',
  20.     typically refrigerators and freezers, and for sump pumps and
  21.     laundry appliances.
  22.  
  23.     The CEC does not mandate as many GFCIs.  In particular, there
  24.     is no requirement to protect kitchen outlets, or most garage or
  25.     basement outlets.  Basement outlets must be protected if you
  26.     have a dirt floor, garage outlets if they're near the door to
  27.     outside.  Bathrooms and most exterior outlets must have GFCIs.
  28.  
  29.     Even if you are not required to have GFCI protection, you may
  30.     want to consider installing it anyway.  Unless you need a GFCI
  31.     breaker (see below), the cost is low.  In the U.S., GFCI
  32.     outlets can cost as little as US$8.  (Costs are a bit higher in
  33.     Canada:  C$12.)  Evaluate your own risk factors.  Does your
  34.     finished basement ever get wet?  Do you have small children?
  35.     Do you use your garage outlets to power outdoor tools?  Does
  36.     water or melted snow ever puddle inside your garage?
  37.  
  38. Subject: Where shouldn't I use a GFCI?
  39.  
  40.     GFCIs are generally not used on circuits that (a) don't pose a
  41.     safety risk, and (b) are used to power equipment that must run
  42.     unattended for long periods of time.  Refrigerators, freezers,
  43.     and sump pumps are good examples.  The rationale is that GFCIs
  44.     are sometimes prone to nuisance trips.  Some people claim that
  45.     the inductive delay in motor windings can cause a momentary
  46.     current imbalance, tripping the GFCI.  Note, though, that most
  47.     GFCI trips are real; if you're getting a lot of trips for no
  48.     apparent reason, you'd be well-advised to check your wiring
  49.     before deciding that the GFCI is broken or useless.
  50.  
  51. Subject: What is the difference between a GFCI outlet and a GFCI breaker?
  52.  
  53.     For most situations, you can use either a GFCI outlet as the
  54.     first device on the circuit, or you can install a breaker with
  55.     a built-in GFCI.  The former is generally preferred, since GFCI
  56.     breakers are quite expensive.  For example, an ordinary GE
  57.     breaker costs ~US$5; the GFCI model costs ~US$35.  There is one
  58.     major exception:  if you need to protect a ``multi-wire branch
  59.     circuit'' (two or more circuits sharing a common neutral wire),
  60.     such as a Canadian-style kitchen circuit, you'll need a
  61.     multi-pole GFCI breaker.  Unfortunately, these are expensive;
  62.     the cost can range into the hundreds of dollars, depending on
  63.     what brand of panel box you have.  But if you must protect such
  64.     a circuit (say, for a pool heater), you have no choice.
  65.  
  66.     One more caveat -- GFCI outlets are bulky.  You may want to use
  67.     an oversize box when installing them.  On second thought, use
  68.     large (actually deep) boxes everywhere.  You'll thank yourself for it.
  69.  
  70.     Incidentally, if you're installing a GFCI to ensure that one
  71.     specific outlet is protected (such as a bathroom), you don't
  72.     really have to go to all of the trouble to find the first
  73.     outlet in the circuit, you could simply find the first outlet
  74.     in the bathroom, and not GFCI anything upstream of it.  But
  75.     protecting the whole circuit is preferred.
  76.  
  77.     When you install a GFCI, it's a good idea to use the little
  78.     "ground fault protected" stickers that come with it and mark
  79.     the outlets downstream of the GFCI.  You can figure out which
  80.     outlets are "downstream", simply by tripping the GFCI with the
  81.     test button and see which outlets are dead.
  82.  
  83. Subject: What's the purpose of the ground prong on an outlet, then?
  84.  
  85.     Apart from their use in electronics, which we won't comment on,
  86.     and for certain fluorescent lights (they won't turn on without
  87.     a good ground connection), they're intended to guard against
  88.     insulation failures within the device.  Generally, the case of
  89.     the appliance is connected to the ground lead.  If there's an
  90.     insulation failure that shorts the hot lead to the case, the
  91.     ground lead conducts the electricity away safely (and possibly
  92.     trips the circuit breaker in the process).  If the case is not
  93.     grounded and such a short occurs, the case is live -- and if
  94.     you touch it while you're grounded, you'll get zapped.  Of
  95.     course, if the circuit is GFCI-protected, it will be a very
  96.     tiny zap -- which is why you can use GFCIs to replace
  97.     ungrounded outlets (both NEC and CEC).
  98.  
  99.     There are some appliances that should *never* be grounded.  In
  100.     particular, that applies to toasters and anything else with
  101.     exposed conductors.  Consider:  if you touch the heating
  102.     electrode in a toaster, and you're not grounded, nothing will
  103.     happen.  If you're slightly grounded, you'll get a small shock;
  104.     the resistance will be too high.  But if the case were
  105.     grounded, and you were holding it, you'd be the perfect path to
  106.     ground...
  107.  
  108. Subject: Why is one prong wider than the other?  Polarization
  109.  
  110.     Nowadays, many two-prong devices have one prong wider than the
  111.     other.  This is so that the device could rely (not guaranteed!)
  112.     on one specific wire being neutral, and the other hot.
  113.     This is particularly advantageous in light fixtures, where the
  114.     the shell should neutral (safety), or other devices which want to
  115.     have an approximate ground reference (ie: some radios).
  116.  
  117.     Most 2-prong extension cords have wide prongs too.
  118.  
  119.     This requires that you wire your outlets and plugs the right
  120.     way around.  You want the wide prong to be neutral, and the
  121.     narrow one hot.  Most outlets have a darker metal for the
  122.     hot screw, and lighter coloured screw for the neutral.
  123.     If not, you can usually figure out which is which by which
  124.     prong the terminating screw connects to.
  125.  
  126. Subject: What kind of outlets do I need in a kitchen?
  127.  
  128.     The NEC requires at least two 20 amp ``small appliance
  129.     circuits'' for kitchens.  The CEC requires split-duplex
  130.     receptacles.  Outlets must be installed such that no point is more
  131.     than 24" (NEC) (900 mm CEC) from an outlet.  Every counter wider
  132.     than 12" (NEC) or 300 mm (CEC) must have at least one outlet.
  133.     The circuit these outlets are on may not feed any outlets except
  134.     in the kitchen, pantry, or dining room.  Furthermore, these circuits
  135.     are in addition to any required for refrigerators, stoves, microwaves,
  136.     lighting, etc.  Non-dedicated outlets within 6' of a sink *must* be
  137.     protected by a GFCI (NEC only).
  138.  
  139.     Split duplex receptacles are fed with a 220V circuit.  The tab
  140.     is broken on the hot side of the outlet, and one hot goes to
  141.     the upper outlet, and the other hot goes to the lower outlet.
  142.     The neutral connects to both outlets through one screw.  When
  143.     "carrying through" to another outlet, the neutral must be
  144.     pigtailed, such that removing the outlet, or having the neutral
  145.     connection fall off doesn't cause the neutral to disconnect
  146.     from downstream outlets.
  147.  
  148. Subject: Where must outlets and switches be in bathrooms?
  149.  
  150.     There must be at least one outlet in each bathroom, adjacent to
  151.     the sink, in addition to any outlet that may be incorporated in
  152.     the light fixture.  All such outlets *must* be GFCI-protected.
  153.  
  154. Subject: What is Romex/NM/NMD?  What is BX?  When should I use each?
  155.  
  156.     Romex is a brand name for a type of plastic insulated wire.
  157.     Sometimes called non-metallic sheath.  The formal name is NM.
  158.     This is suitable for use in dry, protected areas (ie: inside
  159.     stud walls, on the sides of joists etc.), that are not subject
  160.     to mechanical damage or excessive heat.  Most newer homes are
  161.     wired almost exclusively with NM wire.  There are several
  162.     different categories of NM cable.
  163.  
  164.     BX cable -- technically known as armored cable or "AC" has a
  165.     flexible aluminum or steel sheath over the conductors and is
  166.     fairly resistant to damage.
  167.  
  168.     TECK cable is AC with an additional external thermoplastic
  169.     sheath.
  170.     
  171.     Protection for cable in concealed locations: where NM or AC cable
  172.     is run through studs, joists or similar wooden members, the outer
  173.     surface of the cable must be kept at least 32mm/1.25" (CEC & NEC)
  174.     from the edges of the wooden members, or the cable should be protected
  175.     from mechanical injury.  This latter protection can take the form of
  176.     metal plates (such as spare outlet box ends) or conduit.
  177.  
  178.     [Note: inspector-permitted practise in Canada suggests that armored
  179.     cable, or flexible conduit can be used as the mechanical protection,
  180.     but this is technically illegal.]
  181.  
  182.     Additional protection recommendations (these are rules in the
  183.     Canadian codes - they are reasonable answers to the vague
  184.     references to "exposed to mechanical damage" in both the NEC
  185.     and CEC):
  186.  
  187.         - NM cable should be protected against mechanical damage
  188.           where it passes through floors or on the surface of walls
  189.           in exposed locations under 5 feet from the floor.
  190.           Ie: use AC instead, flexible conduit, wooden guards etc.
  191.         - Where cable is suspended, as in, connections to furnaces
  192.           or water heaters, the wire should be protected.  Canadian
  193.           practise is usually to install a junction or outlet
  194.           box on the wall, and use a short length of AC cable
  195.           or NM cable in flexible conduit to "jump" to the appliance.
  196.           Stapling NM to a piece of lumber is also sometimes used.
  197.         - Where NM cable is run in close proximity to heating
  198.           ducts or pipe, heat transfer should be minimized by
  199.           means of a 25mm/1" air space, or suitable insulation
  200.           material (a wad of fiberglass).
  201.         - NM cable shall be supported within 300mm/1' of every box
  202.           or fitting, and at intervals of no more than 1.5m/5'.
  203.           Holes in joists or studs are considered "supports".
  204.           Some slack in the cable should be provided adjacent to
  205.           each box.  [while fishing cable is technically in violation,
  206.           it is permitted where "proper" support is impractical]
  207.         - 2 conductor NM cable should never be stapled on edge.
  208.           [Knight also insists on only one cable per staple, referring
  209.           to the "workmanship" clause, but this seems more honoured
  210.           in the breach...]
  211.         - cable should never be buried in plaster, cement or
  212.           similar finish.
  213.         - cable should be protected where it runs behind baseboards.
  214.         - Cable may not be run on the upper edge of ceiling joists
  215.           or the lower edges of rafters where the headroom is more
  216.           than 1m (39").
  217.  
  218.     Whenever BX cable is terminated at a box with a clamp, small
  219.     plastic bushings must be inserted in the end of the cable to
  220.     prevent the clamps forcing the sharp ends of the armor through
  221.     the insulation.
  222.  
  223.     BX is sometimes a good idea in a work shop unless covered by
  224.     solid wall coverings.
  225.  
  226.     In places where damage is more likely (like on the back wall of
  227.     a garage ;-), you may be required to use conduit, a
  228.     UL- (or CSA-) approved metal pipe.  You use various types of
  229.     fittings to join the pipe or provide entrance/exit for the
  230.     wire.
  231.  
  232.     Service entrances frequently use a plastic conduit.
  233.  
  234.     In damp places (eg: buried wiring to outdoor lighting) you will
  235.     need special wire (eg: CEC NMW90, NEC UF).  NMW90 looks like
  236.     very heavy-duty NMD90.  You will usually need short lengths of
  237.     conduit where the wire enters/exits the ground.  [See underground
  238.     wiring section.]
  239.  
  240.      Thermoplastic sheath wire (such as NM, NMW etc.) should not be
  241.      exposed to direct sunlight unless explicitly approved for that
  242.      purpose.
  243.     
  244.      Canada appears to use similar wire designations to the US,
  245.      except that Canadian wire designations usually include the
  246.      temperature rating in Celsius.  Eg: "AC90" versus "AC".
  247.     In the US, NM-B is 90 degrees celcius.
  248.  
  249.     NOTE: local codes vary.  This is one of the items that changes
  250.     most often.  Eg: Chicago codes require conduit *everywhere*.
  251.     There are very different requirements for mobile homes.
  252.     Check your local codes, *especially* if you're doing anything
  253.     that's the slightest out of the ordinary.
  254.  
  255.     Wire selection table (incomplete - the real tables are enormous,
  256.     uncommon wire types or applications omitted)
  257.  
  258.     Condition            Type    CEC    NEC
  259.  
  260.     Exposed/Concealed dry        plastic    NMD90    NM
  261.                     armor    AC90    AC
  262.                         TECK90
  263.  
  264.     Exposed/Concealed damp        plastic    NMD90    NMC
  265.                     armor    ACWU90
  266.                         TECK90
  267.  
  268.     Exposed/Concealed wet        plastic    NMWU90
  269.                     armor    ACWU90
  270.                         TECK90
  271.     
  272.     Exposed to weather        plastic    NMWU
  273.                         TW etc.
  274.                     armor    TECK90
  275.     
  276.     Direct earth burial/        plastic    NMWU*    UF
  277.     Service entrance            RWU
  278.                         TWU
  279.                     armor    RA90
  280.                         TECK90
  281.                         ACWU90
  282.     [* NMWU not for service entrance]
  283.  
  284.  
  285. Subject: Should I use plastic or metal boxes?
  286.  
  287.     The NEC permits use of plastic boxes with non-metallic cable
  288.     only.  The reasoning is simple -- with armored cable, the box
  289.     itself provides ground conductor continuity.  U.S. plastic
  290.     boxes don't use metal cable clamps.
  291.  
  292.     The CEC is slightly different.  The CEC never permits cable
  293.     armor as a grounding conductor.  However, you must still
  294.     provide ground continuity for metallic sheath.  The CEC also
  295.     requires grounding of any metal cable clamps on plastic boxes.
  296.  
  297.     The advantage of plastic boxes is comparatively minor even for
  298.     non-metallic sheathed cable -- you can avoid making one ground
  299.     connection and they sometimes cost a little less.  On the other
  300.     hand, plastic boxes are more vulnerable to impacts.  For
  301.     exposed or shop wiring, metal boxes are probably better.
  302.  
  303. Subject: Junction box positioning?
  304.  
  305.     A junction box is a box used only for connecting wires together.
  306.  
  307.     Junction boxes must be located in such a way that they're accessible
  308.     later.  Ie: not buried under plaster.  Excessive use of junction
  309.     boxes is often a sign of sloppy installation, and inspectors may
  310.     get nasty.
  311.  
  312. Subject: Can I install a replacement light fixture?
  313.  
  314.     In general, one can replace fixtures freely, subject to a few
  315.     caveats.  First, of course, one should check the amperage
  316.     rating of the circuit.  If your heart is set on installing half
  317.     a dozen 500 watt floodlights, you may need to run a new wire
  318.     back to the panel box.  But there are some more subtle
  319.     constraints as well.  For example, older house
  320.     wiring doesn't have high-temperature insulation.  The excess
  321.     heat generated by a ceiling-mounted lamp can and will cause the
  322.     insulation to deteriorate and crack, with obvious bad results.
  323.     Some newer fixtures are specifically marked for high
  324.     temperature wire only.  (You may find, in fact, that your
  325.     ceiling wiring already has this problem, in which case
  326.     replacing any devices is a real adventure.)
  327.  
  328.     Other concerns include providing a suitable ground for some
  329.     fluorescent fixtures, and making sure that the ceiling box and
  330.     its mounting are strong enough to support the weight of a heavy
  331.     chandelier or ceiling fan.  You may need to install a new box
  332.     specifically listed for this purpose.  A 2x4 across the ceiling
  333.     joists makes a good support.  Metal brackets are also available
  334.     that can be fished into ceilings thru the junction box hole and
  335.     mounted between the joists.
  336.  
  337.     There are special rules for recessed light fixtures such as
  338.     "pot" lamps or heat lamps.  When these are installed in insulated
  339.     ceilings, they can present a very substantial fire hazard.
  340.     The CEC provides for the installation of pot lamps in insulated
  341.     ceilings, provided that the fixture is boxed in a "coffin" (usually
  342.     8'x16"x12" - made by making a pair of joists 12" high, and covering
  343.     with plywood) that doesn't have any insulation.  (Yes, that's 8 *feet*
  344.     long)
  345.  
  346.     NEC rules are somewhat less stringent.  They require at least 3"
  347.     clearance between the fixture and any sort of thermal insulation.
  348.     The rules also say that one should not obstruct free air movement,
  349.     which means that a CEC-style ``coffin'' might be worthwhile.
  350.     Presumably, that's up to the local inspector.  [The CEC doesn't
  351.     actually mandate the coffin per-se, this seems to be an inspector
  352.     requirement to make absolutely certain that the fixture can't get
  353.     accidentally buried in insulation.  Ie: if you have insulation blown
  354.     in later.]
  355.  
  356.     There are now fixtures that contain integral thermal cutouts and
  357.     fairly large cases that can be buried directly in insulation.  They are
  358.     usually limited to 75 watt bulbs, and are unfortunately, somewhat
  359.     more expensive than the older types.  Before you use them, you should
  360.     ensure that they have explicit UL or CSA approval for such uses.
  361.     Follow the installation instructions carefully; the prescribed location
  362.     for the sensor can vary.
  363.  
  364.     There does not yet appear to be a heat lamp fixture that is approved
  365.     for use in insulation.  The "coffin" appears the only legal approach.
  366.  
  367. Subject: What does it mean when the lights brighten when a motor starts?
  368.  
  369.     This usually means that the neutral wire in the panel is
  370.     loose.  Depending on the load balance, one hot wire may end up
  371.     being more than 110V, and the other less than 110V, with
  372.     respect to ground.  This is a very hazardous situation - it can
  373.     destroy your electronic equipment, possibly start fires, and in
  374.     some situations electrocute you (ie: some US jurisdictions
  375.     require the stove frame connected to neutral).
  376.  
  377.     If this happens, contact your electrical authority immediately
  378.     and have them come and check out the problem.
  379.  
  380.     Note: a brief (< 1 second) brightening is sometimes normal with
  381.     lighting and motors on the same 220V with neutral circuit.  A
  382.     loose main panel neutral will usually show increased brightness
  383.     far longer than one second.  In case of doubt, get help.
  384.  
  385. Subject: What is 3 phase power?  Should I use it?  Can I get it in my house?
  386.  
  387.     Three phase power has three "hot" wires, 120 degrees out of
  388.     phase with each other.  These are usually used for large motors
  389.     because it is more "efficient", provides a bit more starting torque,
  390.     and because the motors are simpler and hence cheaper.
  391.  
  392.     You're most likely to encounter a 3 phase circuit that shows
  393.     110 volts between any hot and ground, and 208 volts between
  394.     any two hots.  The latter shows the difference between a normal
  395.     220V/110V common neutral circuit, which is 240 volts between the
  396.     two hots.  There are 3 phase circuits with different voltages.
  397.  
  398.     Bringing in a 3 phase feed to your house is usually
  399.     ridiculously expensive, or impossible.  If the equipment you
  400.     want to run has a standard motor mount, it is *MUCH* cheaper to
  401.     buy a new 110V or 220V motor for it.  In some cases it is
  402.     possible to run 3 phase equipment on ordinary power if you have
  403.     a "capacitor start" unit, or use a larger motor as a
  404.     (auto-)generator.  These are tricky, but are a good solution if
  405.     the motor is non-standard size, or too expensive or too big to
  406.     replace.  The Taunton Press book ``The Small Shop'' has an
  407.     article on how to do this if you must.
  408.  
  409.     Note that you lose any possible electrical efficiency by using
  410.     such a converter.  The laws of thermodynamics guarantee that.
  411.  
  412. Subject: Is it better to run motors at 110 or 220?
  413.  
  414.     Theoretically, it doesn't make any difference.  However, there
  415.     is a difference is the amount of power lost in the supply
  416.     wiring.  All things being equal, a 220V motor will lose 4 times
  417.     less power in the house wiring than a 110V motor.  This also
  418.     means that the startup surge loss will be less, and the motor
  419.     will get to speed quicker.  And in some circumstances, the
  420.     smaller power loss will lead to longer motor life.
  421.  
  422.     This is usually irrelevant unless the supply wires are more
  423.     than 50 feet long.
  424.  
  425. Subject: What is this nonsense about 3HP on 110V 15A circuits?
  426.  
  427.     It is a universal physical law that 1 HP is equal to 746
  428.     watts.  Given heating loss, power factor and other inefficiencies,
  429.     it is usually best to consider 1 HP is going to need 1000-1200
  430.     watts.  A 110V 15A circuit can only deliver 1850 watts to a motor,
  431.     so it cannot possibly be more than approximately 2 HP.  Given rational
  432.     efficiency factors, 1.5HP is more like it.
  433.  
  434.     Some equipment manufacturers (Sears in particular, most router
  435.     manufacturers in general ;-) advertise a HP rating that is far
  436.     in excess of what is possible.  They are giving you a "stall
  437.     horsepower" or similar.  That means the power is measured when
  438.     the motor is just about to stop turning because of the load.
  439.     What they don't mention is that if you kept it in that
  440.     condition for more than a few seconds hopefully your breaker
  441.     will trip, otherwise the motor will melt -- it's drawing far
  442.     more current than it can continuously.
  443.  
  444.     When comparing motors, compare the continuous horsepower.  This
  445.     should be on the motor nameplate.  If you can't find that figure,
  446.     check the amperage rating, which is always present.
  447.  
  448. Subject: How do I convert two prong receptacles to three prong?
  449.  
  450.     Older homes frequently have two-prong receptacles instead
  451.     of the more modern three.  These receptacles have no safety
  452.     ground, and the cabling usually has no ground wire.  Neither
  453.     the NEC or CEC permits installing new 2 prong receptacles anymore.
  454.  
  455.     There are several different approaches to solving this:
  456.         1) If the wiring is done through conduit or BX, and the
  457.            conduit is continuous back to the panel, you can connect
  458.            the third prong of a new receptacle to the receptacle
  459.            box.  NEC mainly - CEC frowns on this practise.
  460.         2) If there is a copper cold water pipe going nearby, and
  461.            it's continuous to the main house ground point, you can
  462.            run a conductor to it from the third prong.
  463.         3) Run a ground conductor back to the main panel.
  464.         4) Easiest: install a GFCI receptacle.  The ground lug
  465.            should not be connected to anything, but the GFCI
  466.            protection itself will serve instead.  The GFCI
  467.            will also protect downstream (possibly also two prong
  468.            outlets).  If you do this to protect downstream outlets,
  469.            the grounds must not be connected together.  Since it
  470.            wouldn't be connected to a real ground, a wiring fault
  471.            could energize the cases of 3 prong devices connected
  472.            to other outlets.  Be sure, though, that there aren't
  473.            indirect ground plug connections, such as via the sheath
  474.            on BX cable.
  475.  
  476.     The CEC permits you to replace a two prong receptacle with a three
  477.     prong if you fill the U ground with a non-conducting goop.
  478.     Like caulking compound.  This is not permitted in the NEC.
  479.  
  480. Subject: Are you sure about GFCIs and ungrounded outlets?
  481.     Should the test button work?
  482.  
  483.     We're sure about what the NEC and CEC say.  Remember, though,
  484.     that your local codes may vary.  As for the TEST button -- there's
  485.     a resistor connecting the LOAD side of the hot wire to the LINE
  486.     side of the neutral wire when you press the TEST button.  Current
  487.     through this resistor shows up as an imbalance, and trips the GFCI.
  488.     This is a simple, passive, and reliable test, and doesn't require
  489.     a real ground to work.  If your GFCI does not trip when you press
  490.     the TEST button, it is very probably defective or miswired.  Again:
  491.     if the test button doesn't work, something's broken, and potentially
  492.     dangerous.  The problem should be corrected immediately.
  493.  
  494.     The instructions that come with some GFCIs specify that the ground
  495.     wire must be connected.  We do not know why they say this.  The
  496.     causes may be as mundane as an old instruction sheet, or with the
  497.     formalities of UL or CSA listing -- perhaps the device was never
  498.     tested without the ground wire being connected.  On the other hand,
  499.     UL or CSA approval should only have been granted if the device
  500.     behaves properly in *all* listed applications, including ungrounded
  501.     outlet replacement.  (One of us called Leviton; their GFCIs are
  502.     labeled for installation on grounded circuits only.  The technician
  503.     was surprised to see that; he agreed that the NEC does not require
  504.     it, and promised to investigate.)
  505.  
  506. Subject: How should I wire my shop?
  507.  
  508.     As with any other kind of wiring, you need enough power for all
  509.     devices that will be on simultaneously.  The code specifies
  510.     that you should stay under 80% of the nominal capacity of the
  511.     circuit.  For typical home shop use, this means one circuit for
  512.     the major power tools, and possibly one for a dust collector or
  513.     shop vac.  Use at least 12 gauge wire -- many power tools have
  514.     big motors, with a big start-up surge.  If you can, use 20 amp
  515.     breakers (NEC), though CEC requires standard 20A receptacles
  516.     which means you'd have to "replug" all your equipment.  Lights
  517.     should either be on a circuit of their own -- and not shared
  518.     with circuits in the rest of the house -- or be on at least two
  519.     separate circuits.  The idea is that you want to avoid a
  520.     situation where a blade is still spinning at several thousand
  521.     RPM, while you're groping in the dark for the OFF switch.
  522.  
  523.     Do install lots of outlets.  It's easier to install them in the
  524.     beginning, when you don't have to cut into an existing cable.
  525.     It's useful if at least two circuits are accessible at each
  526.     point, so you can run a shop vac or a compressor at the same
  527.     time as the tool you really want.  But use metal boxes and
  528.     plates, and maybe even metal-sheathed cable; you may have
  529.     objects flying around at high speeds if something goes a bit
  530.     wrong.
  531.  
  532.     Note that some jurisdictions have a "no horizontal wiring"
  533.     rule in workshops or other unfinished areas that are used
  534.     for working.  What this means is that all wiring must be
  535.     run along structural members.  Ie: stapled to studs.
  536.  
  537.     Other possible shop circuits include heater circuits, 220V
  538.     circuits for some large tools, and air compressor circuits.
  539.     Don't overload circuits, and don't use extension cords if you
  540.     can help it, unless they're rated for high currents.  (A coiled
  541.     extension cord is not as safe as a straight length of wire of
  542.     the same gauge.  Also, the insulation won't withstand as much
  543.     heat, and heat dissipation is the critical issue.)
  544.  
  545.     If your shop is located at some remove from your main panel,
  546.     you should probably install a subpanel, and derive your shop
  547.     wiring from it.  If you have young children, you may want to
  548.     equip this panel with a cut-off switch, and possibly a lock.
  549.     If you want to install individual switches to ``safe''
  550.     particular circuits, make sure you get ones rated high enough.
  551.     For example, ordinary light switches are not safely able to
  552.     handle the start-up surge generated by a table saw.  Buy
  553.     ``horsepower-rated'' switches instead.
  554.  
  555.     Finally, note that most home shops are in garages or unfinished
  556.     basements; hence the NEC requirements for GFCIs apply.  And
  557.     even if you ``know'' that you'd never use one of your shop
  558.     outlets to run a lawn mower, the next owner of your house might
  559.     have a different idea.
  560.  
  561.     Note: Fine Woodworking magazine often carries articles on shop
  562.     wiring.  April 1992 is one place to start.
  563.  
  564. Subject: Underground Wiring
  565.  
  566.     You will need to prepare a trench to specifications, use
  567.     special wire, protect the wire with conduit or special plastic
  568.     tubing and possibly lumber (don't use creosoted lumber, it rots
  569.     thermoplastic insulation and acts as a catalyst in the corrosion
  570.     of lead).  The transition from in-house to underground wire is
  571.     generally via conduit.  All outdoor boxes must be specifically
  572.     listed for the purpose, and contain the appropriate gaskets,
  573.     fittings, etc.  If the location of the box is subject to immersion
  574.     in water, a more serious style of water-proof box is needed.  And
  575.     of course, don't forget the GFCIs.
  576.  
  577.     The required depths and other details vary from jurisdiction to
  578.     jurisdiction, so we suggest you consult your inspector about
  579.     your specific situation.
  580.  
  581.     A hint: buy a roll of bright yellow tape that says "buried power
  582.     line" and bury it a few inches above where the wire has been placed.
  583.  
  584. Subject: Aluminum wiring
  585.  
  586.     During the 1970's, aluminum (instead of copper) wiring became
  587.     quite popular and was extensively used.  Since that time,
  588.     aluminum wiring has been implicated in a number of house fires,
  589.     and most jurisdictions no longer permit it in new installations.
  590.     We recommend, even if you're allowed to, that do not use it for new
  591.     wiring.
  592.  
  593.     But don't panic if your house has aluminum wiring.  Aluminum
  594.     wiring, when properly installed, can be just as safe as copper.
  595.     Aluminum wiring is, however, very unforgiving of improper
  596.     installation.  We will cover a bit of the theory behind potential
  597.     problems, and what you can do to make your wiring safe.
  598.